Peak charges explained

What is PJM 5CP?

A customer's load in PJM's five highest summer hours sets the next year's capacity tag. PJM takes the five highest daily peaks of its whole system from June to September, on weekdays that are not holidays, with the demand response it dispatched added back. Each utility turns a customer's average load in those five hours into its capacity tag. The tag sets the customer's share of capacity cost for the year from the next June.

At a glance

  • Capacity charge
  • Top 5 days
  • Market-wide peak
  • Billed from next June
One seasonJanFebMarAprMayJunJulAugSepOctNovDec

Top 5 peak days each season, June 1 to September 30, non-holiday weekdays only, measured hourly. Measured on PJM's total load, with demand response added back, in Eastern time.

What a peak costs

At published prices, a MW in the counted peaks costs about $120,000 a year, shared by 5 peaks, so each MW cut in one of them saves about $24,000. It is the price per MW of the charge, not a customer's bill, which its utility or supplier sets.

What we forecast

Once PJM's data is connected, we forecast PJM's total hourly load and the chance that each summer weekday is one of the five.

Where the forecast simplifies

  • PJM publishes the demand response it added back only in October, so on a day with dispatched demand response the peak we track can sit slightly below PJM's.
  • We forecast PJM's five hours, not a customer's tag. Each utility adjusts the tag for losses and scaling in its own way.

Sources